Permit: T04PL01851

Parcel: 120091320


Addresses:

414 E MICHIGAN DR


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04PL01851

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HTR FLU VENT IS OK T & P VALVE AND DRAIN IS OK
10/19/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CAN NOT HAVE A UNION IN GAS LINE BY WATER HTR. SHALL PROVIDE AN APPROVED COUPLING 2)RE TEST SYSTEM
10/18/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)SHALL USE FACTURY WRAP SCOTCH COAT PIPE UNDERGROUND 2)SHALL PROVIDE APPROVED COUPLINGS IN GAS LINE 3)SHALL REMOVE UNION IN LINE 4)SHALL USE APPROVED TAPE PRIMER THEN APPLY 10 MIL TAPE TO FITTINGS UNDERGROUND 5)SHALL PROVIDE 90 DEGREES @ END OF T&P SRAIN WITH NO THREAD @ END 6)RE TEST SYSTEM 10 LBS MIN
10/14/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*1)W/H NEED DOUBLE WALL VENT THROUGH ROOF 2)PTR LINE TO GO OUTSIDE 3)NEED PRESSURE TEST 10 LBS MIN. 4)HEATER NOT ALLOWED W/O VENT 5)NEED 12" OF COVER ON GAS LINE. STOPPED INSP.