Permit: T04PL01826

Parcel: 133400570


Addresses:

1038 N VIA TERRADO

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/12/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/1)GAS PRESSURE TEST IS OK 2)GAS SHUT OFF VALVES OK 3)WATER HTR FLU VENT, T&P VALVE & DRAIN IS OK. 4)GAS PACK UAS? ROOF OK
10/11/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MINIMUM REQUIRED DEPTH IS 12' TO TOP OF PIPE 2) GAS PRESSURE IT TO LOW-3 POUNDS
10/11/2004 PLUMBING - FINAL Denied PROVIDE MINIMUM 10 POUND PRESSURE TEST ON GAS SYSTEM. BEST TO GO OVER 10 POUND BONDING JUMPER NOT ADEQUATE SIZE. USE MINIMUM #10 WIRE. PROVIDE MINIMUM 3 SCREWS IN EACH JOINT OF WATER HEATER VENT. TAPE IS NOT NECESSARY