Permit: T04PL01804

Parcel: 134082100


Addresses:

8541 E BEVERLY ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/12/2004 PLUMBING - FINAL Approved IVRS - Inspection :*
11/09/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/PLEASE READ NOTES FROM 10/07/04 INSPECTION AND FOLLOW ALL OF THEM
10/07/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/REMOVE TAPE FROM VENT CONNECTOR ON WATER HEATER VENT-NEED TO SEE CONNECTIONS. EXTEND T&P DRAIN LINE INTO DRAIN PAN. PLUG OUTLET ON DRAIN PAN. PROVIDE A 125 PSI PESSURE RELIEF OUTSIDE ON WATER PIPE & PROVIDE A PETITION OF APPEAL FOR ALTERNATE METHOD OF RUNNING THE T&P DRAIN LINE & LEAVE ON SITE. PROVIDE HIGH & LOW COMBUSTION AIR VENTS TO WATER HEATER & FURNACE ENCLOSURE.
10/05/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/PLEASE SCHEDULE AN INSPECTION WHEN AN ADULT WILL BE PRESENT