Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T04PL01788
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2004 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :*/CORRECTIONS HAVE BEEN MADE AS PER LAST REQUEST. 1 FURNACE ONLY - TEST OK. CALL GAS CO AT 889-1888. CARD AT METER SET | |
10/29/2004 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*/SEE NOTES FROM 10/7/04, PROVIDE BONDING OF BUILDING GAS SYSTEM, UN USED VENT CONNECTED TO HANGING HEATER TO BE CAPPED. PROVIDE ROOF ACCESS AT NEXT INSPECTION AND ACCESS TO ALL GAS PIPING | |
10/07/2004 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : 1) I NEED ACCESS TO ENTIRE NEW PIPING. 2) CAP ALL UNUSED BRANCHES A SHUT OFF ALONE IS NOT SUFFICIENT. 3) SUPPORT PIPE PER UPC. CHANGE OF DIRECTION, UNIONS, ETC. |