Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection :* |
| 10/05/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Partial Approval |
IVRS - Inspection :*/1)SCOTCHCOAT PIPE TO BE BEDDED AND SHADED WITH APPROVED FILL-NATIVE SOILS TO ROCKY 2)ALL FITTINGS AND MARRED SECTIONS TO BE PRIMED AND TAPED. 3)A THREAD PROTECTOR IS NOT AN APPROVED COUPLING. COUPLING TO HAVE STANDARD TAPER THREAD. THREAD PROTECTOR HAS RUNNING THREAD |