Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/ | |
| 10/11/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PLEASE READ ALL NOTES FROM 10/6/04 INSPECTION 2)TEST IS NOT IN PLACE AT THIS TIME 3)WATER HEATER TEMPERATURE PRESSURE RELIEF DRAIN SHALL GRAVITY DRAIN TO DAYLIGHT (NO FLEX CAN BE USED) USE APPROVED RIDGED PIPE |
|
| 10/06/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PROVIDE A MIN. 10 LB TEST ON GAS SYSTEM. GAUGE IS READING 2 PSI. 2)USE APPROVED PRIMER & TAPE ON ALL JOINTS IN THE TRENCH 3)USE A ROOF JACK WHERE GAS PIPE PENETRATES THE ROOF & PROVIDE A BLOCK & CLAMP. 4)CONNECT THE GAS PIPE TO THE EXISTING PIPE IN LAUNDRY ROOM. INSTALLL THE WATER HEATER. PROVIDE A PERMIT IF INSTALLING A NEW WATER HEATER. DO NOT USE A UNION TO CONNECT TO EXISTING PIPE. 5)USE APPROVED SHUT OFF VALVES AT APPLIANCES 6)CAP OFF THE UNUSED GAS PIPE TO STOVE. RECALL FOR INSPECTION. ALSO, THE DRAWING YOU PROVIDED SHOWS 1"PIPE. 3/4" PIPE WAS USED. REPLACE 3/4" PIPE & USE 1" AS PER DRAWING |
|
| 10/05/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PERMIT ON FRONT DOOR, BUT NOBODY HOME. |