Permit: T04PL01742

Parcel: 137101970


Addresses:

5510 S CANADA DR

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/12/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*/1)ALL CORRECTIONS HAVE BEEN MADE
10/11/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT @ WATER HTR FLU VENT APPLIANCE COLLAR AND @ EACH JOINT 2)SHALL RUN AND TERMINATE T&P DRAIN TO DAYLIGHT WITH PITCH AND TERMINATE 6" ABOVE CRADE. YOU MAY USE CPVC, COPPER OR GALVANIZED MATERIAL 3)SHALL TAPE PRIMER & WRAP 90DEGREES @ RISER 4)SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES @ ALL APPLIANCES 5)RE TEST SYSTEM TO 10LBS MIN.
10/05/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
1) NO ONE HOME!
10/01/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*