Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/10 PSI TEST FROM METER NEW 3/4" SCOTCH COAT UNDER GROUND UP NOW PIPING OVER HEAD TO FURANCE, WATER HEATER AND STOVE. OK GAS CARD AT METER 889-1888 | |
| 09/24/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/23/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/10 PSI PRESSURE TEST FROM METER NEW 3/4 SCOTCHCOAT UNDERGROUND TO BUILDING EXISTING SERVICE ENTRANCE TO WATER HEATER, FURANCE, AND STOVE. WILL NOT HOLD PRESSURE. |
|
| 09/21/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : 1) MINIMUM OF 10 PSI SHALL BE ON SYSTEM AT TIME OF INSPECTION WITH NO PRESSURE PROP FOR 15 MIN 2) PRIME & TAPE ALL TOOL MARKS ON UNDERGROUND PIPING 3) WHERE UNIONS ARE NECESSARY LEFT & RIGHT NIPPLES & COUPLINGS SHALL BE USED. 4) PROVIDE BONDING CLAMP AT WIRE AT COLD WATER SERVICE LOCATION. 5) PROVIDE SEPERATE FULL SIZE RIDGID DRAIN FOR WATER HEATER TEMPERATURE & PRESSURE ? DRAIN, GRAVITY DRAIN TO DAYLIGHT.TERMINATE AT 90 PER CENT DOWN 6" TO 24" ABOVE FINISH GRADE. 6) VENT FROM WATER HEATER & FURNACE TO BE 3' ABOVE TOP OF COOLER INTAKE W? WITH IN 10'OF COOLER INTAKE. |