Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) WATER HTR FLU VENT, T & D VALVE & DRAIN OK. 4) NOTE: APPEAL FORM HAS BEEN OBTAINED AND FILED 5) FURNACE FLU VENT IS OK. | |
| 09/21/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SHALL PROVIDE T & P VALVE AND DRAIN FOR WATER HTR 2) SHALL REMOVE UNION IN LINE 3) SHALL SCREW DOWN WATER HTR FLU VENT WITH (3) SHEET METAL SCREWS PER JOINT AND AT APPLIANCE COLLAR 4) RETEST SYSTEM 5) SHALL PROVIDE APPEAL FORM FOR ALTERNATE METHOD OF T & P INSTALLATION IF REQUIRED |