Permit: T04PL01707

Parcel: 128030630


Addresses:

5731 E SCARLETT ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/22/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/20/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/1)FITTING AT CONNECTION BETWEEN SCOTCH COAT & BLK PIPE AT METER IS A THREAD PROTECTOR AND NEEDS TO BE REPLACED WITH AN APPROVED COUPLING. 2)PLEASE PRIME & TAPE ALL UNDERGROUND PIPE WITH TOOL MARKS AND FITTINGS 3)WATER HEATER TEMPERATURE PRESSURE RELIEF TO BE OPENABLE AND CRAVITY DRAIN TO DAYLIGHT. 4)ALL APPLIANCES TO HAVE APPROVED AGA OR CSA GAS VALVES 5)ROOF TOP UNIT REQUIRES APPROVED GAS VALVE AND THEN FLEX CONNECTION TO UNIT 6)PROVIDE BONDING OF BUILDING GAS PIPING
09/17/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*