Permit: T04PL01628

Parcel: 110034820

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
11/29/2004 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*/M-H #4 VACUUM TEST OK. M-H #3 VACUUM TEST OK. M-H #2 VACUUM TEST OK. H-H #1 VACUUM TEST OK.
09/28/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/1)FROM M-H #1 - HCS #2 - TEST OK 3.5LBS 4.50 MIN 2)FROM M-H #1 - TO M-H #5 PCWWM WITH HCS #1 3.5 LBS - 10.00 MIN TEST OK. 3)FROM M-H #2 TO HCS #4 3.5LBS FOR 6 MIN. 4)FROM M-H #3 TO M-H #4 3.5LBS FOR 9.50 MIN. HCS #5 TEST OK 3.5LBS FOR 5.5 MIN.
09/10/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MAIN LINES ONLY ALSO HCS FOR #1. HCS #2=6" HCS #4 APROX LOCATION=6" HCS #6=6" SDR 35-NEED REVISIOR HCS #8=6" SDR 35
PLEASE PROVIDE APPROVED REVISED PLAN BY NEXT INSP LETTER ON JOB AT THIS TIME FOR REVISIONS PROVIDE PLAN. CONTRACTOR WILL PROVIDE VARIFICATION OF GRADE. ALSO TEST AT LATER DATE/WILL REQUIRE VACUUM TEST ON M-H