Permit: T04PL01603

Parcel: 113042370


Addresses:

818 E FREEMAN PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/21/2004 PLUMBING - FINAL Approved IVRS - Inspection :* 1) GAS FINAL OK. OK FOR GAS 2) CARD LEFT AT METER
09/17/2004 PLUMBING - FINAL Denied IVRS - Inspection :
DENIED. REMOVE THE UNION FROM 1/2" GAS PIPE TO STOVE & USE A REVERSE THREAD COUPLING & NIPPLE. ?? & TAPE TO 6" ABOVE GRADE. RETEST SYSTEM. PIPE IN TRENCH IS OK. OK TO BACKFILL
09/08/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)SECURE PERMIT FOR WATER HEATER
2)EXPOSE ALL PIPING.
T&P RELIEF DRAIN TO BE HARD PIPED
REQUIRE DI ELECTRIC CONNECTION BETWEEN GALVANIZED AND COPPER