Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/CORRECTION MADE GAS CARD AT METER 889-1888 | |
| 09/03/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/10 PSI AIR TEST ON NEW PIPING AT METER TO 1ST 90DEGREE THEN EXISTING TO WATER HEATER, STOVE, & ROOF TOP UNIT OK 1)WATER HEATER TO BE IN WEATHER PROOF ENCLOSURE 2)WATER HEATER T&P DRAIN TO BE RIDGID PIPED FULL SIZE TO 6" FROM FINISH GRADE 3)ALL APPLIANCES TO HAVE AGA OR CSA APPROVED GAS VALVES 4)PROVIDE BONDING OF BUILDING GAS PIPING 5)WATER HEATER TO HAVE VENT INSTALLED TO ABOVE ROOF LEVAL WITH APPROVED CAP 6)RIDGID NIPPLE TO BE USED T PENATRATE ROOF TOP UNIT APPLIANCE HOUSING |