Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PER SECTION 1211.10 USE RIGHT AND LEFT NIPPLE TO REPLACE UNION-WRAP/PROTECT GAS LINE 6" ABOVE GRADE 2) PER SECTION 516.5 SINGLE WALL VENTS SHALL MAINTAIN 6" CLEAR FROM COMBUSTIBLE MATERIAL ALL PER 1994 UPC. BE ADVISED A HAZARD EXISTS ON UNIT 01028 PER SECTION 516.5 |