Permit: T04PL01526

Parcel: 13109063B


Addresses:

5815 E 24TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/08/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/03/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/5819 IS OK FOR GAS
1)SYSTEM TO HOLD MINIMUM 10 PSI FOR 15 MINUTES
2)WATER HEATER T&P DRAIN TO BE RIDGID PIPING & GRAVITY DRAIN TO DAYLIGHT
3)WATER HEATER VENT TO BE 3' ABOVE TOP OF COLLER INTAKE WITH APP CAP
09/02/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :11 PSI AIR TEST FROM NEW METER LOCATION OVERHEAD TO WATER HEATER, EXISTING BUILDING SERVICE TO FURNACES AND STOVE OK
PROVIDE UPPER & LOWER COMBUSTION AIR FOR WATER HEATER ENCLOSURE
PROVIDE BONDING OF BUILDING GAS PIPING
VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE TOP OF COOLER