Permit: T04PL01501

Parcel: 120051940


Addresses:

4508 S 13TH AV

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/07/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK FOR UNDERGROUND GAS LINE ONLY. 2) OK TO BACKFILL TRENCH
11/29/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SHALL PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM
2) SHALL PROVIDE MINIMUM 18 GAUGE TRACER WIRE ON UNDERGROUND GAS LINE
3) REMOVE UNION IN LINE BY GAS METER
4) SHALL PROVIDE AGA OR CSA SHUT OFF VALVE AT WATER HEATER
5) T & P DRAIN SHALL TERMINATE TO DAYLIGHT
6) REPLACE ASBESTOS FLU VENT WITH B-VENT AT WATER HTR AND PROVIDE (3) SHEET METAL SCREWS PER JOINT