Permit: T04PL01467

Parcel: 132160320


Addresses:

1435 E BENSON HY #D

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/25/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HTR FLU VENT, T & P VALVE AND DRAIN IS OK 4) EXISTING FURNACE OK
08/18/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED
1)UNIONS ARE NOT ALLOWED SHALL REPLACE WITH RIGHT & LEFT NIPPLE OR CONNECT SOLID
2)SHALL REPLACE ALL OLD GAS SHUT OFF VALVES THAT DO NOT HAVE THE AGA OR CSA MARKINGS ON VALVE
3)CHECK SYSTEM THESE COULD BE MORE CODE VIOLATIONS
4)RE-TEST SYSTEM 10 LBS MIN.