Permit: T04PL01443


Addresses:

10249 E RITA RD

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
04/25/2005 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
02/22/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*PARTIAL APPROVAL
MANHOLE #2 VACUUM TEST OK.
MANHOLE #9 VACUUM TEST OK
MANHOLE #10 VACUUM TEST OK
AIR TESTING & VACUUM TESTING FROM EXISTING MANHOLE #44 THRU MANHOLES #1 THRU MANHOLE #10 INLCUDING 4" HCS LATERALS PER PLAN COMPLETE OK. 1) WILL NEED TO SEE CERTIFICATE OF COMPLETION FROM P.D.E.Q. FOR FINAL APPROVAL.
02/17/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* PARTIAL APPROVAL
4 PSI AIR TEST FROM MANHOLE # 6 TO # 7 INCLUDING 4" HCS ?? TO FRY'S NORTHWEST CORNER OK.
4PSI AIR TEST FROM MANHOLE # 9 TO # 44 EXISTING OK.
4 PSI AIR TEST FROM MANHOLE # 9 TO #10 OK.
4 PSI AIR TEST FROM MANHOLE #9 4"HCS LATERAL TO SOUTHEAST OK PAD3
4 PSI AIR TEST FROM MANHOLE #9 4" HCS LATERAL TO EAST OK. PAD 2
4 PSI AIR TEST FROM MANHOLE # 9 4"HCS LATERAL TO NORTH WEST OK PAD 4
4 PSI AIR TEST FROM MANHOLE # 10 4" HCS LATERAL THRU 2-WAY C/O NORTHEAST TO END OF LINE FOR FUTURE PAD 1 OK
4PSI AIR TEST FROM MANHOLE # 8 4"HCS LATERAL TO FRY'S NORTHEAST CORNER OK.
4PSI AIR TEST FROM MANHOLE #3 4'' HCS LATERAL TO PAD 7 OK.
4 PSI AIR TEST FROM MANHOLE #2 4" HCS LATERAL TO PAD 6 OK
4PSI AIR TEST FROM MANHOLE #1 4" HCS LATERAL TO PAD 5 OK.
02/16/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* 5 PSI AIR TEST FROM MANHOLE # 5 TO #6 OK
4 PSI AIR TEST FROM MANHOLE #4 TO #5, #3 TO #4, #2 TO #3, #1 TO #2, OK. 4 PSI AIR TEST FROM MANHOLE # 1 TO #44 EXISTING OK.
02/15/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :* NOT READY
02/14/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :* NOT READY
02/11/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* PARTIAL APPROVAL 4 PSI AIR TEST FROM MANHOLE # 8 TO # 7 OK
02/09/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* MANHOLE #'S 1,3,4,5,6,7,8 VACUUM TEST OK # 2 DENIED WILL REQUIRE RETEST
02/07/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
01/26/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
01/24/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
12/29/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
12/29/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER DOWN STREAM OF MANHOLE #10 CORRECTION MADE
12/23/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MANHOLE #9 BASE OK 1)MANHOLE #10 REQUIRES CORRECT FLEXIBLE CONNECTION. HUB FOR SDR 35 IS IN WRONG DIRECTION FOR FLOW ON DOWN STREAM SIDE.
12/22/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/NO CHANGES FROM 12/21/04 INSPECTION EXCEPT BACKFILL
12/21/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER APP. 10' FROM MANHOLE #44 UP STREAM APP. 175' TOWARD MANHOLE #9 OK PENDING NOTES FROM 11/23/04
10249 8" SEWER FROM MANHOLE #44 TO MANHOLE #9 OK. 8" SEWER FROM MANHOLE #9-#10 OK. 4" SEWER FROM MANHOLE #9 TO 5' FROM PAD 1 OK PENDING NOTES FROM 11/23/04
12/20/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/1)8" SITE SEWER FROM M.H. #44 UPSTREAM TO M.H. #9 IS OK
12/17/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MANHOLE BASE #1 & #2 OK. 8" SEWER FROM 10' FRONT MANHOLE #44 UP STREAM APP 52' OK PENDING NOTES FROM 11/23/04
12/15/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM MANHOLE #1 TO MANHOLE #44 OK PENDING NOTES FROM 11/23/04
12/14/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* 8" SEWER MANHOLE #2 TO MANHOLE #1 OK. 4" SEWER FROM MANHOLE #1 WEST TO 5' FROM FUTURE BUILDING OK 8" SEWER FROM MANHOLE #1 TO 10" FROM EXISTING MANHOLE #44 OK ?? NOTES FROM 11/23/04
12/13/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM MANHOLE #2 TOWARD MANHOLE #1 APP. 100' OK. 4" SEWER WEST FROM MANHOLE #2 PENDING NOTES FROM 11/23/04
12/09/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MANHOLE #3 & MANHOLE #4 BASE OK. 8" SEWER FROM MANHOLE #4 TO MANHOLE #2 TO 15' NORTH OF MANHOLE #2 OK PENDING NOTES FROM 11/23/04
12/06/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/ 1) 8" SEWER FROM MANHOLE #4 TO MANHOLE#3 OK AND STUB FROM MANHOLE#3 TOWARD (APP. 13') MANHOLE #2 OK PENDING NOTES FROM 11/23/04 INSPECTION
12/03/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/ 1) 8" SEWER FROM MANHOLE #5 TO MANHOLE #4 OK PENDING NOTES FROM 11/23/04
12/01/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM MANHOLE #5 TO MANHOLE #4 PENDING NOTES FROM 11/23/04 INSP.
11/30/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM MANHOLE #6 TO MANHOLE #5 OK. MANHOLE #6 & #5 BASE OK. 8" SEWER FROM MANHOLE #5 60' TOWARD MAHHOLE #4 OK. SEE NOTES FROM 11/23/04 INSP.
11/29/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM MAN HOLE #7 TO MAN HOLE #6 INCLUDING 4" HCS LATERAL FOR BUILDING OK. 8" SEWER FORM MAN HOLE #6 APP 80' SOUTH TOWARD MAN HOLE #5 OK. SEE NOTES FROM 11/23/04
11/26/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
11/24/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MANHOLE #7 & #8 BASE OK. 8" SEWER FROM MANHOLE #7 TO MANHOLE #6 REQUIRES FITTING AND STUB FOR HCS. 8" SEWER FROM MANHOLE #6 60' SOUTH OK. SEE NOTES FROM 11/23/04 INSPECTION
11/23/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM MANHOLE #7 TO MANHOLE #8 OK. 1)WILL NEED AIR TEST ON SEWER, VACUUM TEST ON MANHOLES, VERIFICATION OF GRADE, MANDREU? & MIRROR AT LATER DATE