Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2004 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :*/ 1) CORRECTIONS MADE OK, OK FOR GAS, OK TO COVER 2) UCC LEFT AT METER | |
| 08/11/2004 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*/1) SEE CHAPTER 12 GAS PIPING LOCATION-MUST BE A MINIMUM OF 12" DEEP. MAY NOT RUN UNDER ANY BLDG OR STRUCTURE 2)MAKE ALL CONNECTIONS, INSTALL ALL PIPE AND TEST TO 10# 3)VALVES AND FLEXES INSIDE OK |