Permit: T04PL01375

Parcel: 130030450


Addresses:

2608 E CROSBY VISTA

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/11/2004 PLUMBING - FINAL Approved IVRS - Inspection :*
08/05/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :SEAL ALL PENETRATIONS INTO BUILDING
ALL APPLIANCES TO HAVE AGA OR CSA GAS VALVES
VENT FROM FURNACE TO BE DBL WALL THRU ROOF WITH APPROVED CAP WHEN WITHIN 10' OF COOLER INTAKE TO BG 2' ABOVE TOP OF COOLER
WATER HEATER T&P DRAIN TO THERMOSTAT 90 DEG DOWN ON EXTERIOR OF BUILDING
15 PSI AIR TEST NOW 1" FROM METER LOCATION TO DRYER, WATER HEATER STOVE AND FURNACE OK