Permit: T04PL01360

Parcel: 11517180A


Addresses:

1631 N RIVERVIEW BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/04/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
02/21/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/10/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
10/28/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)SHALL PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM 10 LBS MIN 2)SHALL REMOVE UNIONS IN LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLES. 3)WATER HTR REQUIRES A ENCLOSURE 4)SHALL EXTEND WATER HTR T&P DRAIN AND TERMINATE 6" A.F.F. 5)SHALL PROVIDE DBL WALL FLU VENT FOR WATER HTR THRU ROOF 6)SHALL PROVIDE AGA OR CSA GAS VALVES @ ALLL APPLIANCES 7)CAN NOT HAVE A FLEX CONNECTOR PASS THRU CABINET WALL AND CAN NOT CONNECT 2 FLEXES TOGETHER
08/05/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) THIS INSPECTOR URGES THE TENANT TO HIRE A LICENSED PLUMBING CONTRACTOR TO TAKE A LOOK AT THIS WORK: SIZE OF PIPING, LOCATION OF PIPING, APPROVED FITTINGS, VALVES AND APPROVED LOCATIONS