Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection :*/ 1) CORRECTIONS MADE 2) 10 PSI AIR TEST FROM NEW METER LOCATION 3/4" TO EXISTING BLDG ENTRANCE TO WATER HEATER, FURNACE AND COOK TOP OK 3) SEAL YOUR PENETRATION INTO BLDG 4) GAS CARD ON METER |
| 07/27/2004 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection :DENIED. (1) ALL ABOVE GROUND GAS PIPING TO BE SUPPORTED PROPERLY, 6" MINIMUM ABOVE FINISH GRADE, AND APPROVED COUPINGS SHALL BE USED. (2) WATER HEATER TEMPERTURE AND PRESSURE RELIEF TO BE APPROVED MATERIALS FOR DRAIN, CPVC, COPPER, GAW(?) PIPE AND TERMINATE AT 90 DEGREE DOWN AND BE SUPPORT PROPERLY, CRAVITY DRAIN TO DAYLIGHT. (3) BLD GAS PIPING TO BE BONDED TO COLD WATER PIPING WITH BONDING CLAMPS AND #4 COPPER WIRE. (4) VENT(?) FROM WATER HEATER AND FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE TOP OF COOLER SECURED PROPERLY WITH APPROVED VENT CAP. |