Permit: T04PL01305

Parcel: 137052450


Addresses:

818 W LOUISIANA ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/28/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) GAS PRESSURE TEST IS OK 2) ALL CORRECTIONS HAVE BEEN MADE
09/22/2004 PLUMBING - FINAL Denied IVRS - Inspection :
1) SHALL PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM 2) SHALL REPLACE OLD GAS SHUT OFF VALVE FOR RANGE AND REPLACE WITH AGA OR CSA GAS SHUT OFF VALVE. 3) NOTE: CAN NOT HAVE THE FLEX CONNECTOR PASSING THAN CABINET WALL. THIS MUST BE HARD PIPE THEN THE FLEX