Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) 25 PSI AIR TEST NEW SCOTCHCOAT UNDEGROUND FROM METER TO BLDG UP TO WATER HEATER AND ROOF TOP OUT (ONLY) CORRECTION MADE. NO NEW UNIT INSTALLED. GAS CARD AT METER |
| 08/06/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) THIS ADDRESS IS NOT CORRECT. ACTUAL ADDRESS IS 5626 E 26TH ST. UNIT #10 2) HAVE CORRECT PERMITED ADDRESS 3) WATER HEATER TEMP AND PRESSURE RELEASE DRAIN TO BE RIDGID PIPING GRAVITY DRAIN TO DAYLIGHT 4) WATER HEATER CLOSET TO HAVE UPPER AND LOWER COMBUSTION AIR INTAKES 5) WATER HEATER TO HAVE APPROVED VENT CAP 6) HAVE NEW ROOF TOP UNIT ADDED TO PERMIT 7) EXTEND GAS PIPING TO CORRECT DISTANCE FROM NEW ROOF TOP ? FOR FLEX TO BE USED |