Date Description Inspector Results Comments
08/04/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
07/27/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :SHALL PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM NEW & EXISTING
SHALL REMOVE UNIONS IN EXISTING GAS LINE AND REPLACE WITH RIGHT AND LEFT HAND NIPPLES OR CONNECT SOLID
SHALL PROVIDE 3 SHEET METAL SCREENS PER JOINT AND @ APPLIANCE COLLAR FOR WATER HEATER FLU VENT
SHALL PROVIDE APPROVED GAS SHUT OFF VALVE FOR WATER HEATER