Permit: T04PL01276

Parcel: 131132460


Addresses:

6211 E 35TH ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/26/2004 PLUMBING - FINAL Denied IVRS - Inspection :13 PSI AIR TEST FROM MOTOR NOW 1" P.S UNDERGROUND TO BLDG 1" UP OVERHEAD TO EXISTING BLD CONNECTION TO STOVE & FURNACE APPROVED
EXTEND FURNACE VENT UP 2' ABOVE COOLER WHEN WITHIN 10' OF INTAKE
OWNER REMOVED STRUCTURAL OVERHANG FOR UNDERGOUND GAS PIPING
07/22/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SEE 94 UPC SECTION 121.3 ON GAS PIPING LOCATION 2) WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLES AND COUPLINGS SHALL BE USED 3) PROVIDE BONDING OF BLDG GAS PIPING 4) ? VENT FROM FURNACE IS WITHIN 10' OF COOLER INTAKE IT SHALL BE 2' ABOVE TOP OF COOLER 5) RETEST AND CALL BACK IN