Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection :14 PSI TEST FROM NEW MOTOR LOCATION TO WALL HEATERS WATER HEATER AND STOVE OK PROVIDE BONDING CLAMP AT BLD COLD WATER AND CONNECT BONDING WIRE FROM BLD GAS TO IT SECURE GAS PIPING AT MOTOR LOCATION PROPERLY |
|
| 07/16/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) PIPE GAS PIPING TO METER LOCATION 2) HAVE AGA OR CSA APPROVED VALVES AT ALL APPLIANCES LOCATION 3) RIDGID PIPE THRU CABINET SIDE WALL FOR STOVE AND SECURE PIPE PROPERLY 4) PROVIDE BONDING OF BLDG GAS PIPING 5) THEN RETEST ENTIRE GAS SYSTEM MINIMUM 10 PSI FOR 15 MINUTES WITH NO PRESSURE DROP |