Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HEATER FLUE VENT. T & P DRAIN IS OK 4) FURNACE FLU VENT IS OK | |
| 07/19/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) GAS PRESSURE TEST WAS DOWN TO 0 POUNDS, 10 POUND MINIMUM REQUIRED 2) SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES FOR ALL GAS APPLIANCES 3) WATER HEATER REQUIRES T & P DRAIN TO TERMINATE TO DAYLIGHT OR PROVIDE VARIANCE FORM FOR ALTERNATE METHOD OF T & P DRAIN FROM OUR OFFICE 4) WATER HEATER FLU VENT SHALL TERMINATE 3'-0" ABOVE COOLER FLU VENT SHALL BE SECURED WITH (3) SHEET METAL SCREWS PER JOINT AND AT APPLIANCE COLLAR |