Permit: T04PL01238

Parcel: 115155490

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/23/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/1)CORRECTIONS MADE OK 2)OK FOR GAS 3)UCC LEFT AT METER. SW GAS 889-1888
12/07/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/15 PSI PRESSURE TEST FROM METER SCOTCH COAT UNDER GROUND TO STOVE & WATER HEATER (ONLY) OK. 1)PLEASE READ ALL NOTES LEFT BY INSPECTORS AND COMPLETE ALL WORK, THEN CALL IN FOR INSPECTION
12/02/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)PROVIDE MINIMUM 10 PSI PRESSURE TEST AT TIME OF INSPECTION AND NO PRESSURE DROP FOR 15 MINUTES. 2)PROVIDE BONDING ON BUILDING GAS PIPING. 3)ALL UNDERGROUND GAS PIPING TO BE 12" MINIMUM COVER. 4)POROVIDE CORRECT SUPPORT FOR WATER HEATER.