Permit: T04PL01228

Parcel: 13413057N

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04PL01228

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) 175 AMP BREAKER IS OK
08/10/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) SEE NOTES FROM PREVIOUS INSPECTION
08/03/2004 PLUMBING - FINAL Denied IVRS - Inspection :175 AMP BREAKER IS TOO LARGE. SEE DATA PLATE ON WATER HEATER
MAX SHOULD BE NO LARGER THAN 150AMP