Permit: T04PL01164

Parcel: 120081890


Addresses:

126 W OHIO ST #01

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/05/2004 PLUMBING - FINAL Approved IVRS - Inspection :*
07/30/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MAX LENGTH OF FLEX CONNECTOR FOR WATER HTR IS 3'-0" 2) SHALL BOND GAS LINE WITH #6 WIRE MINIMUM TO ELECTRIC PANEL OR WATER BOND
07/23/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/08/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/01/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MUST REMOVE UNION IN LINE BY GAS METER. 2) MUST LOCATE GAS SHUT OFF VALVE MAX 3'0" FROM REGULATOR. 3) MUST PROVIDE MIN. 5'0" OF FLU VENT FOR WTR HTR AND 1" CLEARANCE FROM COMBUSTABLE MATERIAL. 4) MUST USE APPROVED OFF SET ADJUSTABLE 90o FOR WTR HTR FLU VENT. 5) MUST PROVIDE (3) SHEET METAL SCREWS PER JOINT ON FLU VENT AND AT APPLIANCE COLLAR. 6) MUST PROVIDE AGA OR CSA GAS SHUT OFF VALVE FOR RANGE. 7) RETEST THE SYSTEM .