Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) GAS PRESSURE IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE | |
| 04/11/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* NOT READY THIS IS 3RD INSPECTION. NO BODY HOME NO ACCESS. PLEASE REMOVE DOOR TO WATER HEATER FOR INSPECTION. ALSO CORRECTION ON VENT FOR WATER HEATER HAVE NOT BEEN CORRECTED. | |
| 08/30/2004 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*/NOT READY 1)READ OVER LAST INSP REQUEST. COMPLETE ALSO RELIET VALVE NOT IN WORKING ORDER-LEAKING 2ND INSP GLASS GAUGE HAS BROKEN. PLEASE PROVIDE WORKING GAUGE |
|
| 08/27/2004 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED 1)SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES @ ALL APPLIANCES 2)SHALL PROVIDE 93) SHEET METAL SCREWS PER JOINT AND @ APPLIANCE COLLAR FOR WATER HTR FLU VENT 3)SHALL USE REQUIRED TEST GAGE FOR PRESSURE TEST OF 1/10 INCREMENTS 4)SHALL LOCATE SHUT OFF VALVE BEFORE FLEX CONNECTOR @ RANGE 5)SHALL SECURE 3/4" GAS LINE @ WEST WALL BY METER 6)WATER HTR FLU VENT MIN. LENGTH WS 5'-0" FROM APPLIANCE COLAR 7)SHALL PROVIDE GROUND BOND FOR GAS LINE #6 WIRE MIN |