Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/12/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* 1) GAS PRESSURE IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE
04/11/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* NOT READY THIS IS 3RD INSPECTION. NO BODY HOME NO ACCESS. PLEASE REMOVE DOOR TO WATER HEATER FOR INSPECTION. ALSO CORRECTION ON VENT FOR WATER HEATER HAVE NOT BEEN CORRECTED.
08/30/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/NOT READY
1)READ OVER LAST INSP REQUEST. COMPLETE
ALSO RELIET VALVE NOT IN WORKING ORDER-LEAKING
2ND INSP
GLASS GAUGE HAS BROKEN. PLEASE PROVIDE WORKING GAUGE
08/27/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED
1)SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES @ ALL APPLIANCES
2)SHALL PROVIDE 93) SHEET METAL SCREWS PER JOINT AND @ APPLIANCE COLLAR FOR WATER HTR FLU VENT
3)SHALL USE REQUIRED TEST GAGE FOR PRESSURE TEST OF 1/10 INCREMENTS
4)SHALL LOCATE SHUT OFF VALVE BEFORE FLEX CONNECTOR @ RANGE
5)SHALL SECURE 3/4" GAS LINE @ WEST WALL BY METER
6)WATER HTR FLU VENT MIN. LENGTH WS 5'-0" FROM APPLIANCE COLAR
7)SHALL PROVIDE GROUND BOND FOR GAS LINE #6 WIRE MIN