Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) CORRECTIONS MADE. NO GAS CARD NEEDED |
| 07/01/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 15 psi air test from meter new piping overhead to wtr htr, furnace, future stove and dryer approved. 1) SEAL PENETRATION OF PIPING AT EXTERIOR OF HOME. 2) PROVIDE BONDING OF BLD GAS PIPING. 3) PROVIDE RIDGID NIPPLE THRU FURNACE HOUSING. NO GAS CARD NECESSAY. |