Permit: T04PL01066

Parcel: 106122760


Addresses:

1473 W MOHAVE RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/29/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/1)CORRECTIONS MADE OK. 2)OK FOR GAS 3)UCC LEFT AT METER SW GAS 889-1888
09/28/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)PRESSURE TEST OK 2)ALL FITTINGS AND MARRED SECTIONS TO BE FRESHLY PRIMED AND TAPED WITH 10 MIL DOUBLE WRAPPED. WHEN INSTALLING TAPE ALLOW ENOUGH AREA AROUND THE FITTING AND PULL THE TAPE TIGHTLY WHILE WRAPPING
07/13/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/09/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
06/28/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) REQUIRE TEN POUND TEST ON ENTIRE SYSTEM. DO NOT TEST THRU APPLIANCES. 2) BELOW GRADE PIPING TO BE AT LEAST TWELVE INCHES DEEP. 3) WHERE UNIONS ARE NECESSARY RIGHT/LEFT NIPPLE AND COUPLINGS SHALL BE USED. 4) ALL FITTINGS BELOW GRADE TO BE PRIMED AND TAPED. 5) ALL VALVES TO BE AGA OR CSA APPROVED.