Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/1)CORRECTIONS MADE OK. 2)OK FOR GAS 3)UCC LEFT AT METER SW GAS 889-1888 | |
| 09/28/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)PRESSURE TEST OK 2)ALL FITTINGS AND MARRED SECTIONS TO BE FRESHLY PRIMED AND TAPED WITH 10 MIL DOUBLE WRAPPED. WHEN INSTALLING TAPE ALLOW ENOUGH AREA AROUND THE FITTING AND PULL THE TAPE TIGHTLY WHILE WRAPPING | |
| 07/13/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/09/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/28/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) REQUIRE TEN POUND TEST ON ENTIRE SYSTEM. DO NOT TEST THRU APPLIANCES. 2) BELOW GRADE PIPING TO BE AT LEAST TWELVE INCHES DEEP. 3) WHERE UNIONS ARE NECESSARY RIGHT/LEFT NIPPLE AND COUPLINGS SHALL BE USED. 4) ALL FITTINGS BELOW GRADE TO BE PRIMED AND TAPED. 5) ALL VALVES TO BE AGA OR CSA APPROVED. |