Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2004 | PLUMBING - FINAL | Approved | ||
| 06/24/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MUST PROVIDE A WTR HTR ENCLOSURE FOR WTR HTR. 2) MUST SECURE WTR HTR FLU VENT TO APPLIANCE COLLAR AND USE THREE SHEET METAL SCREWS PER JOINT. 3) MUST EXTEND T&P DRAIN WITH 3/4" CPVC, COPPER OR GALVANIZED PIPE, NO THREADS AT END OF PIPE. TERMINATE 6" A.F.F. 4) MUST PROVIDE PERMANENT CAP FOR FLOOR HTR IN FIREPLACE. 5) MUST REMOVE ALL UNIONS IN LINE AND REPLACE WITH RIGHT/LEFT HAND NIPPLE OR COUPLINGS. 6) MUST USE APPROVED TAPE PRIMER - YELLOW IN COLOR - ALLOW TO GET TACKY THEN APPLY 10 MIL. TAPE AROUND ALL FITTINGS AND WRENCH MARKS UNDERGROUND. 7) MUST PROVIDE AGA OR CSA GAS SHUT OFF VALVES. 8) RETEST SYSTEM 10 LBS MIN. |