Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T04PL01020
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2004 | PLUMBING - GAS PRESSURE TEST | Approved | ||
| 06/14/2004 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*/ 1) 10 PSI TEST ON ENTIRE SYSTEM MINIMUM AT TIME OF INSPECTION SHALL BE IN PLACE WITH NO PRESSURE DROP 2) PROVIDE AGA OR CSA APPROVED GAS VALVE AT ALL APPLIANCE LOCATIONS 3) WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLES AND COUPLINGS SHALL BE USED 4) PROVIDE BONDING OF BLDG GAS PIPING 5) WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN TO BE RIDGID FULL SIZE PIPING |