Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/1)GAS PRESSURE TEST IS OK 2)GAS SHUT OFF VALVES OK 3)ALL CORRECTIONS HAVE BEEN MADE | |
| 09/22/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)SHALL REMOVE ALL UNIONS IN LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLES. 2)SHALL PROVIDE A WATER HTR ENCLOSURE EXTERIOR LOCATION. 3)WATER HTR FLU VENT SHALL BE A MIN. ON 5'-0" FROM APPLIANCE COLLAR TO FLU CAP. 4)SHALL EXTEND WATER HTR T&P VALVE DRAIN AND TERMINATE 6" ABOVE SLAB 5)RETEST GAS SYSTEM MIN 10 LBS @ TIME OF INSPECTON. |