Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/ 1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE. | |
| 06/14/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MUST PROVIDE AIR PRESSURE TEST MIN. 10 LBS. 2) MUST PROVIDE WTR HTR ENCLOSURE TO PROTECT WTR HTR FROM ELEMENTS. 3) MUST INSTALL A FLU VENT AND CAP FOR WTR HTR. 4) MUST REMOVE THREADS AT END OF T&P DRAIN. 5) MUST SEAL GAS LINE PENETRATION THRU WALL FOR RANGE. 6) MUST SECURE FURNACE FLU VENT WITH 3 SHEET METAL SCREWS PER JOINT. 7) MUST PROVIDE AN AGA OR CSA GAS VALVE AT FURNACE. |