Permit: T04PL01017

Parcel: 120075150


Addresses:

361 W AVIATION DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/16/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE.
06/14/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MUST PROVIDE AIR PRESSURE TEST MIN. 10 LBS. 2) MUST PROVIDE WTR HTR ENCLOSURE TO PROTECT WTR HTR FROM ELEMENTS. 3) MUST INSTALL A FLU VENT AND CAP FOR WTR HTR. 4) MUST REMOVE THREADS AT END OF T&P DRAIN. 5) MUST SEAL GAS LINE PENETRATION THRU WALL FOR RANGE. 6) MUST SECURE FURNACE FLU VENT WITH 3 SHEET METAL SCREWS PER JOINT. 7) MUST PROVIDE AN AGA OR CSA GAS VALVE AT FURNACE.