Permit: T04PL00992

Parcel: 13315299A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/10/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ INSPECTED AM - LEFT LIST OF CORRECTIONS - RE-INSPECTED PM - 15 PSI PRESSURE TEST EXISTING PIPNG TO WTR HTR, ROOF TOP UNITS AND COOKING EQUIPMENT OK. CORRECTION MADE. GAS CARD AT METER.
06/09/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) 10 PSI MIN. PRESS TEST SHALL HOLD FOR NO LESS THAN 15 MINUTES WITH NO DROP. 2) ALL APPLIANCES ON WHEELS TO HAVE SAFTY CABLES INSTALLED. 3) AGA OR CSA APPROVED GAS VALVE AT SERVICE ENTRY LOCATION. 4) PROVIDE BONDING OF BLD GAS PIPING.