Permit: T04PL00973

Parcel: 135103860

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/09/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ CORRECTION MADE. PETITION OF APPEAL FOR WTR HTR T&P #2004-21 ON SITE. GAS CARD AT METER.