Permit: T04PL00957

Parcel: 131130570


Addresses:

6041 E 33RD ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/04/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/02/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/ 1) NO UNIONS ON IN LINE PIPING. 2) VENT FROM WTR HTR TO BE PROPERLY SECURED TO DRAFT HOOD WITH 3 GALV. SCREWS AT EACH JOINT. 3) PROVIDE BONDING OF BLD GAS PIPING. 4) WTR HTR T&P RELIEF TO GRAVITY DRAIN TO DAYLIGHT AND 90 DOWNWARD OR PROVIDE CITY SIGNED PETITION OF APPEAL WITH INSTALLATION OF ALTERNATE FORM OF T&P RELIEF ON SITE. 5) VENTS FROM WTR HTR AND FURNACE WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE TOP OF COOLER SECURED WITH APPROVED CAPS. 6) ALL PIPING TO BE SECURED WITH 2-HOLE STRAPS OR APPROVED METHOD ESPECIALLY IN WTR HTR CLOSET. RETEST TO 10 PSI MIN. WITH CORRECTIONS FOR NEXT INSP.