Permit: T04PL00910

Parcel: 110110480


Addresses:

4841 E COPPER ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/15/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ CORRECTION MADE - PETITION OF APPEAL FOR ALTERNTE T&P ON SITE. NO. NOT GIVEN.
05/27/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) WTR HTR T&P RELIEF TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE SIGNED PETITION OF APPEAL FORM ON SITE WITH INSTALLATION PER CITY GUIDELINES. 2) WTR HTR TO BE ON CONCRETE FLOOR OR APPROVED STAND. 3) GAS PIPING TO WTR HTR TO BE 6" MIN. ABOVE FINISHED FLOOR.