Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/04/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/ CORRECTION MADE. 11 PSI AIR TEST 1" SCOTCH COAT NEW FROM METER TO NEW 1" BLK OVERHEAD THRU NEW 3/4 SERVICE VALVE TO EXISTING 3/4 HOUSE PIPING TO STOVE, ROOF TOP UNIT AND WTR HTR. PETITION OF APPEAL FOR ALTERNATE FORM OF T&P RELIEF # 2004-60. GAS CARD AT METER. 889-1888. |
| 06/03/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) WHERE UNIONS ARE NECESSARY LEFT/RIGHT NIPPLES AND COUPLINGS SHALL BE USED. 2) HAVE 10 PSI MIN. ON GAS SYSTEM AT TIME OF INSP. 3) INSTALL 125LB PRESSURE RELIEF ON HOSE BIB LOCATION. |
| 05/28/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) GAS SYSTEM TO HOLD 10 PSI MIN. FOR 15 MINUTES MIN. 2) WTR HTR T&P RELIEF TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE CITY SIGNED PETITION OF APPEAL FOR ALTERNATE FORM OF T&P RELIEF WITH INSTALLATION. 3) PROVIDE PROPER BONDING OF BLD GAS PIPING. |