Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04PL00776
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
07/28/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CONTRACTOR TO PAY REFEE. READ YOUR PLUMBING NOTES AND READ INSPECTOR NOTES AND COMPLETE YOUR WORK PRIOR TO CALLING IT IN FOR REINSPECTION |
|
07/20/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection :PLEASE FOLLOW INSTRUCTIONS LEFT BY INSPECTOR OR FACE REFEE | |
07/15/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEE NOTE #2 FROM 6/22/04 2) SEE NOTE #3 FROM 6/22/04 3) ALL ABOVE GRADE COPPER TO BE SUPPORTED 4) SEE NOTE #1 FROM 6/22/04 |
|
06/22/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) PLEASE REVIEW PLBG NOTE "INSULATION" AND COMPLY. 2) GRADE C.O.'S SHOULD BE CUT DOWN TO GRADE. 3) ALL HOSE BIBS REQUIRE ATMOSPHERIC VACUUM BREAKERS AND VB'S ARE NOT INSTALLED UNTIL THE RETAINING SCREW IS BROKEN OFF. 4) IS MGT AWARE THAT THE CLOTHES WASHERS ARE NOT PLBD TO ANY RECOGNIZABLE CODES. I.E. NO VENTS 'S' TRAPS ETC. |