Permit: T04PL00776

Parcel: 10709049B


Addresses:

2445 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T04PL00776

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2004 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*/ 1) CONTRACTOR HAS TRIED TO MAINTAIN 12" DEPTH ON PVC - CONTRACTOR IS SCREENING DIRT FOR FILL. OK TO COVER. 2) BEFORE GAS CARD WILL BE RELEASED ALL WTR HTRS MUST MEET MIN. SAFETY STANDARDS, I.E. T&P RELIEF, REMOVABLEDOORS, ACCESSIBLE SHUT OFF VALVE AT COLD WTR INLET ETC.
05/12/2004 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection DISCUSSED CODE REQUIREMENTS WITH PLBR AND GENERAL CONTRACTOR.
05/11/2004 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PVC YARDWTR PIPING SHALL AT ALL POINTS BE A MIN. OF TWELVE INCHES BELOW GRADE. NOTE - NATIVE SOILS TOO ROCKY FOR BACKFILL. 2) PLBR WOULD DO WELL TO REVIEW ALL OF THE INSP. NOTES.
05/06/2004 PLUMBING - YARD WTR LINE/TEST Denied 1) PLUMBER SHOULD REVIEW APPROVED PLAN TO DETERMINE THE SCOPE AND EXTENT OF HIS WORK 2) ALL WATER HEATER DOORS ARE TO BE REMOVABLE. ALL WATER HEATERS WILL BE INSPECTED FOR SAFETY. ALL WATER HEATERS ARE TO HAVE A VALVE AT THE COLD WATER INLET. 3) HAVE PLUMBER REVIEW INSTALLATION STANDARD #8-315 TRENCHING, COVER AND BACKFILL AS PLASTIC REQUIRES MINIMUM 12" OF COVER, AND NATIVE SOILS ARE INADEQUATE FOR BACKFILL
05/05/2004 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*/ TO AVOID RE-INSPECTION FEES, SEE 103.5.4.2 - 94 UPC.