Permit: T04PL00726

Parcel: 126210600

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T04PL00726

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
05/26/2004 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*/ 20 PSI AIR TEST FROM METER TO POOL HTR ON EXISTING PIPING OK. 20 PSI AIR TEST ON SOME NEW, MOSTLY EXISTING FROM METER TO THREE ROOF TOP UNITS, FIREPLACE, WTR HTR OK. CORRECTION MADE. GAS CARDS AT METER.
04/22/2004 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*/ 1) 10 PSI PRESSURE TEST MIN. ON ENTIRE GAS PIPING SYSTEM. WHAT ABOUT 1½" TO POOL EQUIP. 2) WHERE UNIONS ARE NECESSARY, LEFT/RIGHT NIPPLES AND COUPLINGS SHALL BE USED. 3) PROVIDE BONDING OF BLD GAS PIPING.
04/20/2004 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection 0000*