Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 05/18/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ PLEASE HAVE SOMEONE PRESENT AT TIME OF NEXT INSP TO PROVIDE ACCESS. 10:10 AM. |
| 04/19/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) 10 PSI AIR TEST MUST BE ON ENTIRE SYSTEM AT TIME OF INSP. 2) 12" MIN. COVER ON IRON PIPE BURIED EXTERIOR. 3) UNION TO BE ON BLDG SIDE OF SERVICE VALVE. 4) APPROVED COUPLING TO BE USED - NO THREAD PROTECTORS. 5) WTR HTR VENT SHALL BE TERMINATED PROPERLY. 6) WTR HTR T&P TO BE RIDGID PIPED. 7) WTR HTR TO HAVE UPPER AND LOWER COMBUSTION AIR. THIS MAY NOT BE A COMPLETE LIST. |