Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/15/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION MADE. |
| 04/14/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ O3050 - CORRECTIONS MADE - 10 PSI AIR TEST FROM METER NEW 1" BLK SCH COAT PIPE FROM METER THRU NEW SERVICE VALVE TO ESIXTING WTR HTR, FURNACE AND STOVE PIPING. GAS CARD AT METER S.W. GAS 889-1888. 03090 - 1) PROVIDE PROPER BONDING. 2) PROVIDE FULL SIZE WTR HTR, FURNACE VENT 3' ABOVE COOLER INTAKE WITH APPROVED FULL SIZE CAP. |
| 04/13/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PRIME AND TAPE ALL UNDERGROUND JOINTS IN PIPING. 2) PIPE IN FRONT OF WTR HTR, ACCESS TO BE RE-ROUTED FOR WTR HTR PULL SPACE. 3) RIDGID PIPE THRU PENETRATION OF FURNACE HOUSING. 4) PROVIDE BONDING OF BLD GAS PIPING. 5) T&P DRAIN TO BE 6" FROM FINISH GRADE. 6) VENT FROM FURNACE AND WTR HTR TO BE FULL SIZE AND 3' ABOVE COOLER INTAKE WHEN WITHIN 10'. |
| 04/09/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |