Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04PL00654

Parcel: 126134550


Addresses:

4620 E DOUGLAS ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/15/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ CORRECTION MADE.
04/14/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ O3050 - CORRECTIONS MADE - 10 PSI AIR TEST FROM METER NEW 1" BLK SCH COAT PIPE FROM METER THRU NEW SERVICE VALVE TO ESIXTING WTR HTR, FURNACE AND STOVE PIPING. GAS CARD AT METER S.W. GAS 889-1888. 03090 - 1) PROVIDE PROPER BONDING. 2) PROVIDE FULL SIZE WTR HTR, FURNACE VENT 3' ABOVE COOLER INTAKE WITH APPROVED FULL SIZE CAP.
04/13/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) PRIME AND TAPE ALL UNDERGROUND JOINTS IN PIPING. 2) PIPE IN FRONT OF WTR HTR, ACCESS TO BE RE-ROUTED FOR WTR HTR PULL SPACE. 3) RIDGID PIPE THRU PENETRATION OF FURNACE HOUSING. 4) PROVIDE BONDING OF BLD GAS PIPING. 5) T&P DRAIN TO BE 6" FROM FINISH GRADE. 6) VENT FROM FURNACE AND WTR HTR TO BE FULL SIZE AND 3' ABOVE COOLER INTAKE WHEN WITHIN 10'.
04/09/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*