Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION MADE. |
| 04/06/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 14 PSI AIR TEST FROM METER NEW 3/4" PIPING TO WTR HTR AND FURNACE APPROVED. 1) SECURE ALL GAS PIPING PROPERLY - 2 HOLE STRAPS. 2) PROVIDE PROPER BONDING OF GAS PIPING - 2 BONDING CLAMPS AND #4 OR #6 COPPER WIRE FROM BLD GAS PIPE TO COLDWTR PIPING. GAS CARD AT METER 889-1888. |