Permit: T04PL00555

Parcel: 138100710


Addresses:

6007 S 6TH AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04PL00555

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ALL CORRECTIONS HAVE BEEN MADE
03/30/2004 PLUMBING - FINAL Denied 1) MUST PROVIDE APPROVED DRAWING SHOWING FULL DEVELOPED LENGTH OF GAS LINE AND BTU AND CFH DEMAND ON SITE AT TIME OF INSP. 2) MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM, 10 LBS MIN. 3) MUST PROVIDE TWO 10X10 LOUVER GRILLS LOCATED 12" BELOW CEILING AND 12" ABOVE FLOOR. 4) MUST EXTEND T&P DRAIN AND TERMINATE 6" A.F.F. 5) MUST REMOVE ALL UNIONS IN EXISTING LINE AND REPLACE WITH RIGHT/LEFT HAND NIPPLES. 6) MUST PRIMER AND 10 MIL TAPE ALL EXISTING FITTINGS UNDERGROUND.